Documented range
Air-insulated MV switchgear
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.
East Africa and the Indian Ocean
Electrical projects in Madagascar cover textile production, port facilities and water-treatment installations. A factory in Antananarivo has different requirements from a technical building in Toamasina. Equipment selection should link the required capacity to the available network, the site environment and access from the port. Medium-voltage switchgear, transformers and low-voltage boards can then be specified around the actual installation, including existing equipment and the functions that require backup power.

Documented voltage levels
20 kVNetwork counterpart
JIRAMA — Jiro sy Rano MalagasyJICA’s 2019 TaToM master plan describes 20 kV distribution in the Toamasina agglomeration and historic 5 kV feeders intended for conversion. It also distinguishes a 35 kV upstream link. This local evidence does not establish one voltage for Madagascar. For a JIRAMA connection, confirm the feeder’s present voltage, neutral arrangement and existing substation characteristics before selecting switchgear, protection settings and the transformer ratio.
The reference catalogue includes AIS and RMU classes 12, 24 and 36 kV, and AIS up to 40.5 kV. For nominal 30 or 33 kV networks, examine the 36 kV option against maximum voltage, insulation, current and fault constraints. A 24 kV class does not cover a nominal 30 kV network; 36 kV does not cover 66 kV. Cable U0/U/Um markings require separate validation.
EquipmentToamasina port, managed by SPAT, is a gateway to assess for equipment entering the island. JICA identifies the city in 2026 as a major international logistics hub and supports renewal of its electrical infrastructure. Delivery planning should then follow the actual inland destination, whether a Toamasina facility, an Antananarivo factory or a more distant installation. Transformer weight, lifting arrangements and construction-site access help determine the appropriate final delivery plan.
Configurations are adapted from the Imperium catalogue verified for this version. Confirm the actual reference, documents and availability in the offer; local approval is not automatic.

Documented range
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.

Documented range
Compact ring-distribution configurations; define switching and protection duties.
Published rated voltages: 12 / 24 / 36 kV. Reference catalogue uses SF6 technology.

Documented range
MV/LV transformation with liquid insulation and cooling; project-specific connections and siting.
Published range: 25–2,500 kVA; primary 3.3–36 kV. Agree actual model values.

Documented range
MV compartment, transformer and LV distribution in one assembly; coordinate civil and electrical interfaces.
Published MV classes: 12 / 24 / 36 kV; transformer 100–2,500 kVA depending on configuration.

Documented range
Distribute loads and priority circuits with an arrangement suited to operation and maintenance.
Fixed or withdrawable catalogue configurations; define assembly verification documentation.

Documented range
Prime or standby supply: assess loads, starting and siting before selecting capacity.
Published range: 0.5–3,550 kVA. Confirm the actual duty and offered rating.

Documented range
Copper or aluminium power connections; assess U0/U/Um, laying conditions and accessories together.
Published classes: 6/10 to 18/30 kV. Do not assume suitability for a 33 kV network without validation.
The November 2024 Mandroseza tender illustrates site-specific requirements. It describes existing 5.5 and 30 kV supplies at the water-treatment and pumping complex, with a new pumping station planned at 30 kV. Its specifications refer to Malagasy standards, JIRAMA requirements and selected UTE/NF standards where local references are absent. Submit the applicable tender specifications and connection diagram with your enquiry: these requirements depend on the installation and cannot be inferred solely from its country.
Organise your technical dossierPossible applications, not completed T Afrik project references.
Antananarivo textile production: low-voltage distribution for garment lines, with transformation and production-load separation suited to the building connection.
IndustriesServicesToamasina technical building or warehouse: MV switchgear, transformation and LV boards sized for handling equipment and auxiliary loads.
IndustriesServicesWater treatment and pumping: motor supplies, coordinated protection and backup for essential functions, based on the station’s own network.
IndustriesServicesThe TaToM report distinguishes the 35 kV upstream link from 20 kV distribution. Confirm the current connection voltage and required equipment rating with JIRAMA for the particular site.
Provide connection voltage, motor power and starting method, essential functions and the operator’s specifications. The Mandroseza example shows why supplies must be checked for each installation.
Sources checked on 9 October 2026
Specify weights, dimensions, port, final site, lifting and origin/transport documents. Packing, service and timing depend on the shipment. An Incoterm needs its named place and version; FCA or DAP are options to agree, not universal terms. Check ISPM 15 for regulated raw wood packaging.
Prepare procurement and logisticsTell us about your application, site and technical constraints to prepare a useful equipment consultation.