For South Africa, equipment selection needs the site's distributor, MV voltage and operating conditions. T Afrik prepares enquiries for switchgear, transformation, cables and standby supply serving industrial networks or generation installations, based on the customer's technical dossier.

Illustrative outdoor substation with a distribution transformer
Representative photograph · T Afrik Energy Solutions

Documented voltage levels

11 / 22 / 33 kV

Network counterpart

Eskom or the relevant municipal electricity distributor

Networks and equipment class selection

The cited Eskom standard 240-69125210 describes nominal 11, 22 and 33 kV networks with equipment ratings of 12, 24 and 36 kV. Its scope is outdoor kiosk circuit-breakers, and the authorized revision needs confirmation for the contract. It shows why voltage alone cannot establish suitability of 36 kV equipment: local insulation levels, current, fault duty, protection and site conditions also matter. Identify Eskom or the municipal distributor first, then the particular connection specifications.

[1]

Network voltage and equipment rating are different

The reference catalogue includes AIS and RMU classes 12, 24 and 36 kV, and AIS up to 40.5 kV. For nominal 30 or 33 kV networks, examine the 36 kV option against maximum voltage, insulation, current and fault constraints. A 24 kV class does not cover a nominal 30 kV network; 36 kV does not cover 66 kV. Cable U0/U/Um markings require separate validation.

Equipment

Ports, transit and the final site route

Transnet National Ports Authority administers Durban, Cape Town and Ngqura among other ports; Transnet Port Terminals documents container services there. Match these entry options to the industrial location and inland route. For large equipment, confirm handling methods and package limits with the carrier and agent. Bookings, customs clearance and transfer to the site determine the actual schedule.

[1][2]

Equipment to examine for your project

Configurations are adapted from the Imperium catalogue verified for this version. Confirm the actual reference, documents and availability in the offer; local approval is not automatic.

Illustrative lineup of air-insulated medium-voltage switchgear
· T Afrik Energy Solutions

Documented range

Air-insulated MV switchgear

Incomers, feeders and transformer protection: define board functions and configuration.

Published rated voltages: 12 / 24 / 36 / 40.5 kV.

Illustrative three-phase cast-resin dry-type transformer
· T Afrik Energy Solutions

Documented range

Cast-resin dry-type transformers

A transformation option to assess against room conditions, ventilation and safety requirements.

Published range: 100–3,150 kVA; primary 3.3–36 kV.

Consultation requirements and documents

The cited Eskom documents reference SANS, NRS and operator-specific technical requirements. Synchronized generation, storage or hybrid installations also need information for connection studies; municipally supplied sites follow the relevant municipality's process. Before quoting, specify the applicable editions, model characteristics and contract-required tests. The requirements for a particular device do not constitute general approval of the catalogue.

[1][2]

Organise your technical dossier

Applications to assess

Possible applications, not completed T Afrik project references.

Solar or hybrid generation serving an industrial site: coordinate transformation, MV feeder and protection with the connection study.

IndustriesServices

Industrial network at an elevated site: verify insulation and ambient conditions against distributor and manufacturer requirements.

IndustriesServices

Installation near a port: assess corrosive exposure, enclosures and handling, then arrange continuity for priority loads.

IndustriesServices

Frequently asked questions

Who confirms the grid connection?

Eskom for a site supplied by its network, or the relevant municipal distributor. Eskom's tool explicitly sends municipal sites to their municipality and certain larger connections to the formal application process.

Is 36 kV equipment automatically suitable for 33 kV?

No. The nominal/rated-voltage match is a starting point. Check the required insulation levels and other ratings, the authorized standard edition and the contract schedules.

Sources and verification scope

Sources checked on 9 October 2026

  1. Eskom — Standard 240-69125210: 11/22/33 kV outdoor kiosk circuit-breakers, Rev. 2
  2. Eskom — Generator, energy-storage or hybrid facility grid application, Rev. 13
  3. Eskom — Current grid application tool
  4. Transnet — National Ports Authority
  5. Transnet Port Terminals — Container services
Explore the regional context

Agree shipment responsibilities

Specify weights, dimensions, port, final site, lifting and origin/transport documents. Packing, service and timing depend on the shipment. An Incoterm needs its named place and version; FCA or DAP are options to agree, not universal terms. Check ISPM 15 for regulated raw wood packaging.