Documented range
Air-insulated MV switchgear
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.
Southern Africa
For South Africa, equipment selection needs the site's distributor, MV voltage and operating conditions. T Afrik prepares enquiries for switchgear, transformation, cables and standby supply serving industrial networks or generation installations, based on the customer's technical dossier.

Documented voltage levels
11 / 22 / 33 kVNetwork counterpart
Eskom or the relevant municipal electricity distributorThe cited Eskom standard 240-69125210 describes nominal 11, 22 and 33 kV networks with equipment ratings of 12, 24 and 36 kV. Its scope is outdoor kiosk circuit-breakers, and the authorized revision needs confirmation for the contract. It shows why voltage alone cannot establish suitability of 36 kV equipment: local insulation levels, current, fault duty, protection and site conditions also matter. Identify Eskom or the municipal distributor first, then the particular connection specifications.
The reference catalogue includes AIS and RMU classes 12, 24 and 36 kV, and AIS up to 40.5 kV. For nominal 30 or 33 kV networks, examine the 36 kV option against maximum voltage, insulation, current and fault constraints. A 24 kV class does not cover a nominal 30 kV network; 36 kV does not cover 66 kV. Cable U0/U/Um markings require separate validation.
EquipmentTransnet National Ports Authority administers Durban, Cape Town and Ngqura among other ports; Transnet Port Terminals documents container services there. Match these entry options to the industrial location and inland route. For large equipment, confirm handling methods and package limits with the carrier and agent. Bookings, customs clearance and transfer to the site determine the actual schedule.
Configurations are adapted from the Imperium catalogue verified for this version. Confirm the actual reference, documents and availability in the offer; local approval is not automatic.

Documented range
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.

Documented range
Compact ring-distribution configurations; define switching and protection duties.
Published rated voltages: 12 / 24 / 36 kV. Reference catalogue uses SF6 technology.

Documented range
MV/LV transformation with liquid insulation and cooling; project-specific connections and siting.
Published range: 25–2,500 kVA; primary 3.3–36 kV. Agree actual model values.

Documented range
A transformation option to assess against room conditions, ventilation and safety requirements.
Published range: 100–3,150 kVA; primary 3.3–36 kV.

Documented range
MV compartment, transformer and LV distribution in one assembly; coordinate civil and electrical interfaces.
Published MV classes: 12 / 24 / 36 kV; transformer 100–2,500 kVA depending on configuration.

Documented range
Distribute loads and priority circuits with an arrangement suited to operation and maintenance.
Fixed or withdrawable catalogue configurations; define assembly verification documentation.

Documented range
Prime or standby supply: assess loads, starting and siting before selecting capacity.
Published range: 0.5–3,550 kVA. Confirm the actual duty and offered rating.

Documented range
Pumps, fans and compressors: specify speed, torque, starting and service conditions.
Published voltage range: 1–11 kV. A motor cannot connect directly to every MV incomer.

Documented range
Copper or aluminium power connections; assess U0/U/Um, laying conditions and accessories together.
Published classes: 6/10 to 18/30 kV. Do not assume suitability for a 33 kV network without validation.
The cited Eskom documents reference SANS, NRS and operator-specific technical requirements. Synchronized generation, storage or hybrid installations also need information for connection studies; municipally supplied sites follow the relevant municipality's process. Before quoting, specify the applicable editions, model characteristics and contract-required tests. The requirements for a particular device do not constitute general approval of the catalogue.
Organise your technical dossierPossible applications, not completed T Afrik project references.
Solar or hybrid generation serving an industrial site: coordinate transformation, MV feeder and protection with the connection study.
IndustriesServicesIndustrial network at an elevated site: verify insulation and ambient conditions against distributor and manufacturer requirements.
IndustriesServicesInstallation near a port: assess corrosive exposure, enclosures and handling, then arrange continuity for priority loads.
IndustriesServicesEskom for a site supplied by its network, or the relevant municipal distributor. Eskom's tool explicitly sends municipal sites to their municipality and certain larger connections to the formal application process.
No. The nominal/rated-voltage match is a starting point. Check the required insulation levels and other ratings, the authorized standard edition and the contract schedules.
Sources checked on 9 October 2026
Specify weights, dimensions, port, final site, lifting and origin/transport documents. Packing, service and timing depend on the shipment. An Incoterm needs its named place and version; FCA or DAP are options to agree, not universal terms. Check ISPM 15 for regulated raw wood packaging.
Prepare procurement and logisticsTell us about your application, site and technical constraints to prepare a useful equipment consultation.