Documented range
Air-insulated MV switchgear
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.
North Africa
For an enquiry in Libya, T Afrik organizes equipment selection around the connection point, substation arrangement and construction-site destination. Distribution configurations documented by GECOL help frame an enquiry for feeder renewal, industrial substations and essential-service auxiliaries. Network characteristics and purchasing conditions need confirmation for each project.

Documented voltage levels
11 / 30 kVNetwork counterpart
GECOL — General Electricity Company of LibyaGECOL's 2023 notices document 11/0.4 kV distribution transformers, 30 kV cables and switchgear, and substation arrangements using 11, 30 and 66 kV. The 66 kV level requires separate treatment from 11/30 kV MV assemblies: equipment rated 36 kV is unsuitable for a nominal 66 kV network. For a 30 kV feeder, the marking “36 kV” alone is also insufficient to select equipment. Confirm current, short-circuit withstand, insulation, earthing, protection and substation interfaces. The enquiry needs the voltage actually available at the site and the applicable GECOL specifications.
The reference catalogue includes AIS and RMU classes 12, 24 and 36 kV, and AIS up to 40.5 kV. For nominal 30 or 33 kV networks, examine the 36 kV option against maximum voltage, insulation, current and fault constraints. A 24 kV class does not cover a nominal 30 kV network; 36 kV does not cover 66 kV. Cable U0/U/Um markings require separate validation.
EquipmentTripoli, Misrata and Benghazi are entry gateways documented by the Libyan Ports and Maritime Transport Authority. Their official dossiers include general cargo and containers. Tripoli serves the northwest; Misrata provides an option on the central coastline east of Tripoli; Benghazi provides an option for eastern Libya. Port selection depends on the final destination, equipment dimensions and handling method. For a transformer or prefabricated substation, the enquiry should identify mass, centre of gravity and destination lifting arrangements. The carrier and local agent need to confirm the service, formalities and inland movement before a delivery date is agreed.
Configurations are adapted from the Imperium catalogue verified for this version. Confirm the actual reference, documents and availability in the offer; local approval is not automatic.

Documented range
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.

Documented range
Compact ring-distribution configurations; define switching and protection duties.
Published rated voltages: 12 / 24 / 36 kV. Reference catalogue uses SF6 technology.

Documented range
MV/LV transformation with liquid insulation and cooling; project-specific connections and siting.
Published range: 25–2,500 kVA; primary 3.3–36 kV. Agree actual model values.

Documented range
MV compartment, transformer and LV distribution in one assembly; coordinate civil and electrical interfaces.
Published MV classes: 12 / 24 / 36 kV; transformer 100–2,500 kVA depending on configuration.

Documented range
Distribute loads and priority circuits with an arrangement suited to operation and maintenance.
Fixed or withdrawable catalogue configurations; define assembly verification documentation.

Documented range
Prime or standby supply: assess loads, starting and siting before selecting capacity.
Published range: 0.5–3,550 kVA. Confirm the actual duty and offered rating.

Documented range
Pumps, fans and compressors: specify speed, torque, starting and service conditions.
Published voltage range: 1–11 kV. A motor cannot connect directly to every MV incomer.

Documented range
Copper or aluminium power connections; assess U0/U/Um, laying conditions and accessories together.
Published classes: 6/10 to 18/30 kV. Do not assume suitability for a 33 kV network without validation.

Documented range
Cable family for HV networks and connections; dedicated cable, joint and termination assessment.
Reference catalogue: 36 kV and above. Exact reference and insulation class require consultation.
Preparing a purchase for Libya starts with the customer's specification, enquiry conditions and requirements of the relevant operator. GECOL publishes tenders with technical references and participation conditions specific to each call. To obtain comparable offers, provide the single-line diagram, voltages, capacities, currents and required functions for switchgear, transformers and cables. Documents to review with the manufacturer include technical data, drawings and relevant test evidence where requested. Agree the final document list, language, approvals and acceptance arrangements before ordering. A product's inclusion in the catalogue does not establish GECOL approval or the existence of a FAT report.
Organise your technical dossierPossible applications, not completed T Afrik project references.
Renewal of urban 11/30 kV feeders: check existing switchgear and cable interfaces, then coordinate protection and insulation.
IndustriesServicesElectrical auxiliaries for coastal pumping or desalination facilities: define motor supplies, MV/LV transformation and site conditions.
IndustriesServicesIndustrial services requiring standby power: size the generator and LV board around priority loads and the transfer arrangement.
IndustriesServicesNo. A 36 kV equipment rating is insufficient for a nominal 66 kV network. The 66 kV arrangements documented by GECOL require an appropriate design and equipment range; the 11/30 kV MV selection does not cover them.
Provide the site location, confirmed connection voltage, single-line diagram, capacities and currents, specification and proposed port. GECOL conditions, required documents and supply lead time need confirmation in the enquiry.
Sources checked on 9 October 2026
Specify weights, dimensions, port, final site, lifting and origin/transport documents. Packing, service and timing depend on the shipment. An Incoterm needs its named place and version; FCA or DAP are options to agree, not universal terms. Check ISPM 15 for regulated raw wood packaging.
Prepare procurement and logisticsTell us about your application, site and technical constraints to prepare a useful equipment consultation.