Documented range
Air-insulated MV switchgear
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.
North Africa
For an Algerian electrical enquiry, distinguish the distribution-network connection, customer substation and site loads. T Afrik prepares equipment selection from the technical dossier and project purchasing conditions, including industrial extensions, agricultural electrification and remote installations.

Documented voltage levels
10 / 30 kVNetwork counterpart
Sonelgaz — Distribution; CREG regulatory contextSonelgaz's 2024 report documents 60/10 kV and 60/30 kV substations: 10 and 30 kV MV levels coexist across networks. Confirm the delivery-point voltage before selecting switchgear, transformer and cables. For a 30 kV supply, a 36 kV equipment rating needs checking alongside insulation, current and short-circuit withstand; it does not constitute approval. Network characteristics, protection and interfaces are defined in the distributor's and customer's project dossier.
The reference catalogue includes AIS and RMU classes 12, 24 and 36 kV, and AIS up to 40.5 kV. For nominal 30 or 33 kV networks, examine the 36 kV option against maximum voltage, insulation, current and fault constraints. A 24 kV class does not cover a nominal 30 kV network; 36 kV does not cover 66 kV. Cable U0/U/Um markings require separate validation.
EquipmentSERPORT's official network includes Algiers, Oran, Béjaïa, Skikda and Annaba. Match these gateway options to the site location and cargo type. For electrical-equipment shipments, confirm acceptance of heavy packages or containers with the port, carrier and agent, followed by the inland route. Service availability and the full delivery schedule need confirmation for the particular order.
Configurations are adapted from the Imperium catalogue verified for this version. Confirm the actual reference, documents and availability in the offer; local approval is not automatic.

Documented range
Incomers, feeders and transformer protection: define board functions and configuration.
Published rated voltages: 12 / 24 / 36 / 40.5 kV.

Documented range
Compact ring-distribution configurations; define switching and protection duties.
Published rated voltages: 12 / 24 / 36 kV. Reference catalogue uses SF6 technology.

Documented range
MV/LV transformation with liquid insulation and cooling; project-specific connections and siting.
Published range: 25–2,500 kVA; primary 3.3–36 kV. Agree actual model values.

Documented range
MV compartment, transformer and LV distribution in one assembly; coordinate civil and electrical interfaces.
Published MV classes: 12 / 24 / 36 kV; transformer 100–2,500 kVA depending on configuration.

Documented range
Distribute loads and priority circuits with an arrangement suited to operation and maintenance.
Fixed or withdrawable catalogue configurations; define assembly verification documentation.

Documented range
Prime or standby supply: assess loads, starting and siting before selecting capacity.
Published range: 0.5–3,550 kVA. Confirm the actual duty and offered rating.

Documented range
Pumps, fans and compressors: specify speed, torque, starting and service conditions.
Published voltage range: 1–11 kV. A motor cannot connect directly to every MV incomer.

Documented range
Copper or aluminium power connections; assess U0/U/Um, laying conditions and accessories together.
Published classes: 6/10 to 18/30 kV. Do not assume suitability for a 33 kV network without validation.

Documented range
Cable family for HV networks and connections; dedicated cable, joint and termination assessment.
Reference catalogue: 36 kV and above. Exact reference and insulation class require consultation.
CREG describes connection procedures involving feasibility assessment, quotation, authorizations and installation conformity before energization. Sonelgaz also presents equipment-qualification and laboratory services. For a quotation, obtain the applicable specifications, any qualification requirement for the model and manufacturer, and the expected supporting evidence. Review drawings, ratings and tests against the contract. No Sonelgaz qualification of T Afrik or its products is presumed.
Organise your technical dossierPossible applications, not completed T Afrik project references.
Industrial-zone extension: coordinate the 10 or 30 kV incoming supply, transformation and LV distribution for new workshops.
IndustriesServicesAgricultural-site electrification: define pumping, motor feeders and cables from distances and available capacity.
IndustriesServicesRemote installation with backup: arrange a compact substation, generator and priority-load transfer to suit the site diagram.
IndustriesServicesNo. The cited Sonelgaz documents also show 10 kV. The distributor needs to confirm the delivery-point voltage and project constraints.
Contract specifications and any qualification requirement for the manufacturer and model still need checking. Confirm acceptance arrangements and required documents with the relevant customer.
Sources checked on 9 October 2026
Specify weights, dimensions, port, final site, lifting and origin/transport documents. Packing, service and timing depend on the shipment. An Incoterm needs its named place and version; FCA or DAP are options to agree, not universal terms. Check ISPM 15 for regulated raw wood packaging.
Prepare procurement and logisticsTell us about your application, site and technical constraints to prepare a useful equipment consultation.